Battery Runtime Calculator

Fill in the fields and press Calculate to see the result.

About the Battery Runtime Calculator

Work out how long a battery or battery bank runs a load, from its amp-hours and voltage, the battery type and whether the load goes through an inverter.

Add the hours of backup you want to see the capacity you need, for a UPS, an RV, a boat or a solar system.

How it is calculated

Runtime (h) = Ah × V × usable share ÷ (load W ÷ inverter efficiency)

A battery stores its amp-hours times its voltage in watt-hours: a 100 Ah, 12 V battery holds 1,200 Wh. Not all of it should be used: lead-acid, AGM and gel batteries last much longer if they are discharged to about 50%, while lithium iron phosphate (LiFePO₄) batteries can use about 90%. An inverter that turns 12 V DC into household AC wastes about 10%, so the battery supplies more than the load uses.

The runtime is the usable energy divided by the power drawn. Real runtimes are shorter with high currents (the Peukert effect, strong in lead-acid batteries), in the cold and as batteries age, so leave a margin.

Example

A 100 Ah, 12 V lead-acid battery running a 100 W load through an inverter lasts 5 h 24 min: 600 Wh usable at 111 W. For 8 hours you need 148 Ah at 12 V.

Frequently asked questions

How long will a 100Ah battery last?

At 12 V it stores 1,200 Wh. A lead-acid battery used to 50% runs a 100 W load for about 6 hours on DC, 5.4 hours through an inverter; a LiFePO₄ battery used to 90% runs it about twice as long.

How many amp-hours do I need?

Multiply the load in watts by the hours, divide by the usable share and by the inverter efficiency, then by the battery voltage. 100 W for 8 h through an inverter on a 12 V lead-acid bank: 100 ÷ 0.9 × 8 ÷ 0.5 ÷ 12 = 148 Ah.